Live HVAC charts with a working ductulator - size round and rectangular duct by equal friction or velocity, read duct weight and surface area per lineal foot, check superheat and subcooling, and look up refrigerant PT values.

CalculatorWiser · HVAC Tools

Ductulator & Air Duct Calculator

The slide-rule duct calculator from the job site, live on the web. Set your airflow once — friction, velocity, round size, rectangular equivalents, duct weight and surface area all read out together, just like the wheel.

Ductulator Live · one setting, all readouts

The ductulator comes in more than one form in the real world, so this one does too: a rotating wheel in the classic style, a straight slide rule with weight and surface-area windows, and a digital readout form. All three run the same duct math, and the Imperial / SI toggle applies to whichever you're using. The digital form also carries the multi-material corrections, a flex-duct compression sizing (ASHRAE/ADI method), and a Manual D friction-rate finder.

Ductulator version

Units:

Rotating wheel. Drag the disc (scroll on it, or focus it and use ← →) to turn your airflow under the friction value on the blue band. The round diameter then sits at the black arrow on the green band, and velocity shows in the hub window — one setting, everything read off the wheel.

Reading the wheel: the orange CFM scale is printed on the disc, the blue FRICTION scale on the fixed sleeve. Turn the disc until your CFM sits under the friction you want — the green diameter band has rotated with the disc, and the size at the fixed black arrow (top) is your round duct. Velocity and velocity pressure are in the hub windows, and the rectangular equivalents of that size are listed below the wheel.

Wheel setting
—
CFM under friction
Round Ø at arrow
—
inches · exact
Velocity
—
FPM
Rect. equivalents
—
green-band sizes · full table below

Equivalent rectangular duct sizes

Every row below carries the same airflow at (very nearly) the same friction as the round duct above — ASHRAE equivalent diameter De = 1.30 (a·b)0.625 ÷ (a+b)0.25. Tap a row to select it — its weight, surface area and Width + Depth then read out below, exactly as on the slide rule.

Rectangular ductWidth + DepthArea (sq ft)Velocity (FPM)Eq. round (in)Aspect

Check your own rectangular duct

Duct weight & surface area per lineal foot

Read at the red arrow on the physical chart — here it updates live. Galvanized steel, U.S. standard gauge selected by SMACNA practice from the duct's larger dimension. Surface area is what you need for insulation and liner estimates.

⭕ Round duct — —

Appropriate gauge—
Surface area—
Weight—
Weight — 100 ft run—

▭ Rectangular duct — —

Appropriate gauge—
Surface area—
Weight—
Weight — 100 ft run—
Width Plus Depth — rectangular readout
— inches total
On the slide rule you set the total of width plus depth at the black arrow to read rectangular weight opposite the appropriate gauge. Here: set it by picking a row above — the total is shown here and the weight is in the panel.
Gauge & weight basis
  • Sheet weights used (galvanized, lb per sq ft): 26 ga 0.906 · 24 ga 1.156 · 22 ga 1.406 · 20 ga 1.656 · 18 ga 2.156.
  • Gauge by larger dimension: up to 12″ → 26 ga · 13–30″ → 24 ga · 31–54″ → 22 ga · 55–84″ → 20 ga · over 84″ → 18 ga. Transverse joints, seams and reinforcement add roughly 10–20% on real shop weight.
  • Aluminum weighs about 35% of the steel figures; B. & S. gauge aluminum readouts on the original chart follow the same surface-area numbers.

Air friction chart — live

The classic ASHRAE friction chart the Ductulator wheel is built from: airflow vs. friction loss, with round-duct diameter lines. Your current setting is the orange dot — move the Ductulator and watch it travel.

Reading it the paper way: find your CFM on the bottom scale, go straight up to your duct-size line, then straight left to read friction per 100 ft — and the velocity for that size where the vertical crosses the sloping velocity lines. The calculator above does the same reading instantly.

Superheat & subcooling

The job of the R-410A / R-22 slide calculators, live. Enter pressures and line temperatures; saturation temperature is interpolated from the PT chart below.

Saturation temperature at that pressure—
Superheat
—
Typical targets
  • TXV systems: charge by subcooling — typically 8–12 °F (follow the nameplate; many specify 10 °F).
  • Fixed-orifice / piston: charge by superheat — target moves with indoor wet-bulb and outdoor dry-bulb; roughly 8–18 °F. Low superheat risks floodback, high superheat starves the coil.
  • Let the system run 10–15 minutes steady before trusting either reading.

Airflow — CFM calculator

Two everyday ways to get a CFM number to feed the Ductulator.

By heat load (sensible)

CFM = BTU ÷ (1.08 × ΔT)—

By room air changes

CFM = Volume × ACH ÷ 60—
Rule-of-thumb check: cooling usually wants 350–450 CFM per ton (400 nominal). A 3-ton system ≈ 1,200 CFM.

Pressure–temperature chart

Saturation pressures (psig) — the reference table behind the superheat calculator. For charging reference only; always confirm against the equipment manufacturer's chart.

Temp °FR-410AR-22R-454BR-32

Quick duct-sizing reference

Standard design friction of 0.10″ per 100 ft (0.82 Pa/m on the SI wheel), galvanized steel — the sizes most techs carry in their head, generated by the same math as the Ductulator above. Follows whichever Ductulator version is selected.

CFMRound (in)Velocity (FPM)Typical use
Design velocity guide (why the verdict box complains)
  • Residential branch ducts: 600–900 FPM · trunks 900–1,200 FPM. Above ~900 FPM in a branch, noise complaints start.
  • Commercial mains: 1,200–1,800 FPM; industrial can run higher. Flex duct should stay at or under ~600–700 FPM and be pulled tight — sagging flex can double or triple its rated friction.
  • Return air runs slower and bigger than supply: aim 700–900 FPM on returns.

Built for CalculatorWiser.com. Calculations use ASHRAE equal-friction relationships for standard air (0.075 lb/cu ft) and are for design and field reference — verify critical designs against current ASHRAE / SMACNA standards and local code.

Calculate hvac-charts quickly and easily with our free calculator.

Preguntas frecuentes

¿Esta calculadora es gratuita?

Sí, todas nuestras calculadoras son gratuitas y no requieren registro.

¿Son precisos los resultados?

Los resultados dependen de la fórmula, los datos, los supuestos y el redondeo de cada herramienta. Usa un ejemplo resuelto para comprobar tus datos y contrasta las estimaciones importantes con la fuente o el proveedor correspondiente.

Academia de reparación de equipos antiguos: los 20 cursos
Biblioteca de formación en oficios olvidados
¿Te fue útil?